Tuesday, September 29, 2026
Saturday, September 26, 2026
Solar Controlled Air Cooler Project
![]() |
| Solar Controlled Air Cooler Project |
A "solar-controlled air cooler" is an air cooling system that primarily uses electricity generated from solar panels, often with a smart control mechanism to maximize solar usage and, in hybrid models, seamlessly switch to grid power when needed.
Does Plant Can Produce Electricity on Itself?
![]() |
| Beautiful Orchid Flower |
How Can Plants Generate Electricity?
Do really living plans can generate electricity? If yes, how?
The answer is yes! Living plants can generate electricity, and it is a very simple way. Some scientists are working on it to generate electricity from plants on an economic scale. They have found and are developing technology to generate electricity from living plants without damaging or disturbing their normal lives. They also identified that wet areas like paddy fields or grain-growing lands where soil normally wetty is suitable for electricity harvesting.
Labels:
Clean Electricity,
Electricity & Nature
Why Earthing Switch or Disconnector is Used in Transmission Line?
Labels:
Earthing or Grounding,
Transfer Switch
Location:
Dhaka, Bangladesh
Thursday, September 24, 2026
Understanding How Ultrasound Testing Works for an Electric Motor
Ultrasound testing is a sophisticated non-destructive testing (NDT) method used extensively in the maintenance and inspection of electric motors. It leverages high-frequency sound waves to detect anomalies, faults, or deteriorations within the motor components, ensuring operational efficiency and preventing unexpected failures.
Labels:
DC Motor,
Induction Motor,
Motor-Engineering
Monday, September 21, 2026
Star Delta Starter Line Diagram and Its Working Principle
![]() |
| Fig: Three-phase motor connection diagram with a star-delta starter. |
What is a Star-Delta Starter for Motor Starting?
A star-delta starter is an electrical motor starting device, generally used in large motors to overcome some technical limitations. Star and Delta mean here 2 separate states of motor running: first Star connection and then Delta connection.
The starting current of any heavy
electric motor can be more than 4 times the normal load current it draws when
it has gained speed and has reached its normal running condition.
To overcome this initial high-current starting problem, such an arrangement needs a star connection at starting time, and if the star connection has sufficient torque to run up to 75% to %80 of full load speed, then the motor can be connected in Delta mode.
To overcome this initial high-current starting problem, such an arrangement needs a star connection at starting time, and if the star connection has sufficient torque to run up to 75% to %80 of full load speed, then the motor can be connected in Delta mode.
When the motor is connected to the Delta
configuration, the phase voltage increases by 173% and phase currents increase
by the same ratio. The line current increases three times its value in star
connection.
What Problem Starting a Motor without Star-Delta?
We already know that if the motor starts
simply when connected in Delta, the starting current would be huge just to
be able to start the motor, not for running conditions. To do this would
require -
v Large capacity circuit breakers to allow the start-up surge
current to pass without immediately shutting the motor off.
v Oversized 3-phase power service cables require just for
starting time, but the normal running time is not necessary.
v Large size of coils and contacts on the relays or contractors need to control the motor, but normal running time needs smaller sizes of them.
Sometimes, the utility company also does not
permit the big motor to start without a Star-Delta starter because of system
instability due to switching transients.
How to Wire a Star-Delta Starter for a Motor?
Following the figure below, the power connection between magnetic contactors for Main, Star, Delta, and the motor is shown in the schematic line diagram and wiring diagram for easy wiring.
What is Important During the Star-Delta Transition Period?
It is important that the break between the Star contactor switch OFF
and the Delta contactor switch is ON because the Star contactor must be reliably
quenched before the Delta contactor is activated. During the transition period of switch-over, the motor must be free-running with little deceleration. It is also
important that the switch-over pause is not too long; it may generate a voltage
of its own, and this may add to or subtract from the applied line voltage.
That’s all for the Star-Delta starter for today; here in this article, we discussed only motor starting by 3 magnetic contactors. Star-Delta and solid-state motor starters from different companies are also available in the market now.
STAR-DELTA STARTER CALCULATOR
Starting Current, Torque & Contactor Sizing — IEC 60947-4-1
WAZIPOINT SYSTEM
MOTOR & SUPPLY PARAMETERS
RESULTS
Enter parameters and click CALCULATE.
REFERENCE NOTES
Typical Starting Current Ratio
| Motor Size | Ist/In |
|---|---|
| < 7.5 kW | 5 – 6 |
| 7.5 – 37 kW | 6 – 7 |
| > 37 kW | 6 – 8 |
Per IEC 60034-12 design classes — confirm against the motor nameplate/datasheet where available.
Star Time Guideline
| Motor Size | Star Duration |
|---|---|
| ≤ 7.5 kW | 3 – 5 s |
| 7.5 – 22 kW | 5 – 8 s |
| 22 – 55 kW | 8 – 12 s |
| > 55 kW | 12 – 20 s |
Switch to delta once the motor reaches ~80–85% of synchronous speed. Switching too early causes a high transient current spike.
Overload relay placement: Most panels mount the thermal overload in the delta-connected branch (between KM3 and the motor windings), where it sees only the phase current (~58% FLC) — this is the setting shown above. If your design instead places the relay in the incoming line (in series with KM1), set it to 100% FLC. Confirm against the actual control drawing before commissioning.
Cable sizing: Six conductors run between the starter and the motor (U1, V1, W1, U2, V2, W2), each carrying the phase current shown above (~58% FLC), not the full FLC. Size these per IEC 60364-5-52 / IS 732 using that reduced design current.
Applicability: Star-delta starting reduces both starting current and starting torque to roughly ⅓ of direct-on-line (DOL) values. It requires access to all six motor winding leads, and the motor's delta-connection nameplate voltage must equal the supply voltage. Not suitable where more than ~33% of DOL starting torque is needed under load (loaded conveyors, positive-displacement pumps) — consider a soft starter or VFD instead.
WAZIPOINT SYSTEM — ENGINEERING CALCULATOR
Labels:
Low Voltage System,
Motor-Engineering
Location:
Dhaka, Bangladesh
Subscribe to:
Posts (Atom)
Follow Our Facebook Page
WAZIPOINT // Engineering Reference
FIG. FB-01
Follow WAZIPOINT Engineering
Field guides, standards updates & calculator tools — IEC / BNBC 2020 / PGCB-BPDB-DESCO-DPDC practice notes.
wazipoint.com — engineering reference & field notes
-
What is Bus-bar? Bus-bar is the common header where one or multiple sources poor the power also one or more sources can take power simul...
-
Bangladeshi all National and Regional Bangla Newspaper List in a Single Click
-
Different Rating's Fuses Fuse Rating Calculating Guide The function of a fuse is to break a circuit when a current threshold...
-
How to Calculate PCD (Pitch Circle Diameter)? PCD is the short form of Pitch Circle Diameter ; the Pitch Circle Diameter (PCD...
-
Basic Color Code for Power Cable Basic Colour Code for Electrical Cable and Power Cable International standard IEC 604...
-
Fig: Three-phase motor connection diagram with a star-delta starter . What is a Star-Delta Starter for Motor Starting? A star-delta s...
-
How Calculate Capacitance of Underground Power Cable? Capacitor is nothing but a two parallel metal plate separated by a dielectric...
-
Why Use Direct Online (DOL) and Star-Delta Starter? DOL means the motor is connected directly to the Line ( Direct On Line ) using o...
-
What Happen if DC Voltage is Applied to Transformer Input? Considering the importance we can say a transformer is the most efficien...
-
Different Types of Engineering Discipline s Engineering is traditionally categorized into six primary branches: biomedical, chemical, civil,...




