WAZIPOINT Engineering Science & Technology

Monday, September 21, 2026

Star Delta Starter Line Diagram and Its Working Principle

Fig: Three-phase motor connection diagram with a star-delta starter.

What is a Star-Delta Starter for Motor Starting?



A star-delta starter is an electrical motor starting device, generally used in large motors to overcome some technical limitations. Star and Delta mean here 2 separate states of motor running: first Star connection and then Delta connection.

The starting current of any heavy electric motor can be more than 4 times the normal load current it draws when it has gained speed and has reached its normal running condition. 

To overcome this initial high-current starting problem, such an arrangement needs a star connection at starting time, and if the star connection has sufficient torque to run up to 75% to %80 of full load speed, then the motor can be connected in Delta mode.

When the motor is connected to the Delta configuration, the phase voltage increases by 173% and phase currents increase by the same ratio. The line current increases three times its value in star connection.

What Problem Starting a Motor without Star-Delta?

We already know that if the motor starts simply when connected in Delta, the starting current would be huge just to be able to start the motor, not for running conditions. To do this would require -


v Large capacity circuit breakers to allow the start-up surge current to pass without immediately shutting the motor off.
v Oversized 3-phase power service cables require just for starting time, but the normal running time is not necessary.
v Large size of coils and contacts on the relays or contractors need to control the motor, but normal running time needs smaller sizes of them.

Sometimes, the utility company also does not permit the big motor to start without a Star-Delta starter because of system instability due to switching transients. 

How to Wire a Star-Delta Starter for a Motor?

Following the figure below, the power connection between magnetic contactors for Main, Star, Delta, and the motor is shown in the schematic line diagram and wiring diagram for easy wiring.

Star-Delta Starter Connection
Star-Delta Starter Connection with Control Wiring

What is Important During the Star-Delta Transition Period?




It is important that the break between the Star contactor switch OFF and the Delta contactor switch is ON because the Star contactor must be reliably quenched before the Delta contactor is activated. During the transition period of switch-over, the motor must be free-running with little deceleration. It is also important that the switch-over pause is not too long; it may generate a voltage of its own, and this may add to or subtract from the applied line voltage.

That’s all for the Star-Delta starter for today; here in this article, we discussed only motor starting by 3 magnetic contactors. Star-Delta and solid-state motor starters from different companies are also available in the market now.

Star-Delta Starter Calculator | WAZIPOINT SYSTEM

STAR-DELTA STARTER CALCULATOR

Starting Current, Torque & Contactor Sizing — IEC 60947-4-1

WAZIPOINT SYSTEM

MOTOR & SUPPLY PARAMETERS

RESULTS

Enter parameters and click CALCULATE.

REFERENCE NOTES

Typical Starting Current Ratio
Motor SizeIst/In
< 7.5 kW5 – 6
7.5 – 37 kW6 – 7
> 37 kW6 – 8

Per IEC 60034-12 design classes — confirm against the motor nameplate/datasheet where available.

Star Time Guideline
Motor SizeStar Duration
≤ 7.5 kW3 – 5 s
7.5 – 22 kW5 – 8 s
22 – 55 kW8 – 12 s
> 55 kW12 – 20 s

Switch to delta once the motor reaches ~80–85% of synchronous speed. Switching too early causes a high transient current spike.

Overload relay placement: Most panels mount the thermal overload in the delta-connected branch (between KM3 and the motor windings), where it sees only the phase current (~58% FLC) — this is the setting shown above. If your design instead places the relay in the incoming line (in series with KM1), set it to 100% FLC. Confirm against the actual control drawing before commissioning.
Cable sizing: Six conductors run between the starter and the motor (U1, V1, W1, U2, V2, W2), each carrying the phase current shown above (~58% FLC), not the full FLC. Size these per IEC 60364-5-52 / IS 732 using that reduced design current.
Applicability: Star-delta starting reduces both starting current and starting torque to roughly ⅓ of direct-on-line (DOL) values. It requires access to all six motor winding leads, and the motor's delta-connection nameplate voltage must equal the supply voltage. Not suitable where more than ~33% of DOL starting torque is needed under load (loaded conveyors, positive-displacement pumps) — consider a soft starter or VFD instead.

STAR-DELTA CONNECTION SCHEMATIC


Tuesday, September 15, 2026

Ring Main Units (RMU) in Power Distribution Networks

Ring Main Units in Power Distribution Networks


Ring Main Units in Power Distribution Networks: A Practicing Engineer's Design and Selection Guide

Monday, September 14, 2026

Substation Automation Functions

Electrical Grid Substation Automation Functions

How to Deal with Electrical Grid Substation Automation Functions Professionally?

Substation automation refers to the integration of various control, protection, monitoring, and communication functions within an electrical substation. These functions aim to enhance the efficiency, reliability, and safety of substation operations. Here are some common substation automation functions:

Saturday, September 5, 2026

What is the Distance Relay and How does It Work?

Distance Relay
Zone Detector



A distance relay, also known as a distance protection relay or impedance relay, is a protective device used in power systems to detect and isolate faults on transmission lines or other electrical equipment. Its primary function is to measure the impedance (or distance) between the relay location and the faulted section of the power system.

Distance Relay and Its Working Principle

Monday, August 31, 2026

Electrical Substation Equipment: Insulator and Its Functions

Electrical substations play a critical role in the transmission and distribution of electricity from power generation plants to consumers. Insulators are an essential component of electrical substations, and their primary function is to provide electrical isolation and mechanical support to various equipment and conductors within the substation. Here's a closer look at insulators and their functions:

Insulators Type

Vital Substation Equipment Insulator and Its Different Functions

Electrical Isolation: One of the main functions of insulators is to prevent the flow of electrical current between different conductive elements in the substation. These conductive elements could be overhead power lines, busbars, or other live equipment. By creating a barrier between conductive parts, insulators prevent unwanted electrical arcing or short circuits, ensuring the safe and reliable operation of the substation.

Sunday, August 30, 2026

Buchholz Relay for Power Transformer Protection Device


What Is A Buchholz Relay?






How does a Buchholz Relay Protect Power Transformer?


A Buchholz relay is a protective device used to protect power transformers from internal faults and incipient failures. It is an essential component of a power transformer's protection and monitoring system. The Buchholz relay operates on the principle of detecting abnormal conditions within the transformer's oil-filled tank. Here's how it works and how it protects power transformers:

Follow Our Facebook Page

WAZIPOINT System — Bangladesh engineering community
WAZIPOINT // Engineering Reference FIG. FB-01
Facebook
Follow WAZIPOINT Engineering
Field guides, standards updates & calculator tools — IEC / BNBC 2020 / PGCB-BPDB-DESCO-DPDC practice notes.
wazipoint.com — engineering reference & field notes