What Would be Normal Current Ratings to Design an Electrical Energy Transmission Underground Lines?
Current ratings in accordance
with IEC 59 shall be adopted, unless
otherwise agreed with the Engineer.
Every current carrying part
of the equipment shall be capable of carrying its site rated current
continuously under the Site conditions as specified, and in no case shall the
permitted temperature rise be exceeded.
The current ratings specified
are the continuous current ratings required at the Site, under the specified
maximum temperature and solar gain conditions.
What Would be Short-Time Current Ratings of Underground Cable Transmission Lines?
Electrical equipment shall be
adequately supported and braced to withstand the forces associated with the
maximum short-circuit currents specified or pertaining, whichever is the
greater, and assuming that the inception of the short-circuit is at such a time
that gives maximum peak currents, No provision for current decrement shall be
made unless specifically permitted by the appropriate Standard, or elsewhere in
this specification.
Equipment shall be so
constructed as to withstand the specified maximum short-circuit currents for a
duration of 3 seconds, (with the exception of cables which shall be 1 second
rated) without the temperature exceeding the specified maximum short-time
temperature or value stated in the relevant standard, under these conditions.
The equipment shall be considered as being operated at the maximum permitted
continuous temperature prior to inception of the short-circuit.
The final temperature
attained as a result of the passage of short-circuit current shall not cause
permanent damage, or deterioration sufficient to reduce the normal operating
characteristics below the specified or most onerous operating requirements
whichever is the highest (unless otherwise agreed with the Engineer).
Sponsored:
Sponsored:
What Would be Normal Voltage Ratings for Underground Energy Transmission Cables Lines?
Unless otherwise specifically
stated, any reference to voltage rating shall be deemed to refer to the Nominal
rated voltage or voltages of electrical equipment. Standard voltage levels in
accordance with IEC 38 shall be adopted,
unless otherwise specified or agreed with the Engineer. Transformer rated
voltages shall comply with IEC 76.
All electrical equipment
shall, except where otherwise specified, be capable of continuous operation at
a voltage level in the range of 90 per cent to 110 per cent of the nominal
voltage without deterioration.
Alternating current rotating
electrical machines shall be capable of providing rated output within the
voltage range 95 per cent to 105 per cent of normal rated voltage.
The temperature rise of
electrical equipment continuously operating at the specified minimum or maximum
voltage shall not exceed the temperature rise when operating at nominal voltage
by more than 5 degrees Celsius.
All D.C. equipment shall be
capable of satisfactory continuous operation in the conditions specified when
subjected to the maximum boost voltage output of the associated battery
chargers unless dual battery & charger systems adequately controlled and
interlocked are provided in which case they shall be capable of continuous
operation at the maximum possible float charge voltage.
In addition all D.C equipment
shall perform satisfactorily at D.C. voltage down to 85% of the specified
nominal voltage. Tripping relays and coils etc shall operate down to 80% of the
specified nominal voltage.
Sponsored:
Sponsored:
What Would be Short-Time Voltage Ratings of Underground Power Transmission Lines?
All electrical equipment
shall be so designed such as to withstand abnormal system voltages as required
by the appropriate Standard (unless otherwise specified).
No comments:
Post a Comment
WAZIPOINT:
Thank you very much to visit and valuable comments on this blog post. Keep in touch for next and new article. Share your friends and well-wisher, share your idea to worldwide.