The Most Important and Basic Electrical Types of Equipment, Instrument,s and Meters that You Need to Know Now If You Want to Keep Your Plant Function Properly.
All instruments and meters
shall be fitted with glasses of low reflectivity and shall not cause a pointer
deflection due to electrostatic charging through friction.
All indicating instruments
shall be of the flush-mounted pattern with dust and moisture-proof cases
complying with BS 2011, Classification
00/50/04, and shall comply with BS 89:1977 or IEC 51.
Unless otherwise specified,
all indicating instruments shall have 95mm square cases to DIN standard or
equivalent circular cases.
Instrument dials in general
should be white with black markings and should preferably be reversible where double-scale instruments are specified.
Scales shall be of such
material that no peeling or discoloration will take place with age under humid
tropical conditions.
The movements of all
instruments shall be of the deadbeat type.
Instruments shall be provided
with readily accessible zero adjustments.
Monitoring Equipment and Meters for Electrical Instrument
The mounting height of the center of all indicating instruments shall not exceed 2000mm.
AC ammeters for transformer,
feeder, or interconnector circuits, and DC ammeters for all load circuits except
motors shall have linear scales commencing at zero.
AC and DC ammeters for motor circuits shall have scales commencing at zero and with a compressed overload
portion for the reading of the associated minor starting current.
DC ammeters for the main
battery circuit of DC systems shall have scales with positive and negative
ranges labeled charge and discharge respectively.
Voltmeters for feeders and
transformer circuits shall have expanded scales to display the nominal service
voltage ± 20%.
Wattmeter for feeders shall
have linear positive and negative reading scales to be approved.
VAR meters for all circuits
shall have linear positive and negative reading scales to be approved.
Frequency meters shall be of
the pointer type scaled approximately 45-55Hz, and biased to swing to one end
of the scale on the loss of voltage.
Synchronizing voltmeters
shall be scaled in per-unit values only, to correspond to the above expanded
voltmeter scales.
Synchroscopes should be continuously rated, but if not then at
least 30 minutes rated with an individual on/off switch.
The synchroscopes shall indicate synchronism between
two circuits with the pointer at the “12’0’clock” position only and shall have
arrows on the face to show that the frequency of the “incoming” supply is fast
or slow with respect to the “running” supply. The synchroscope switch shall disconnect both supplies
to the instrument and the instrument pointer shall move at least 450 from the
vertical position when either or both supplies are removed and shall then
remain stationary without any tendency to creep.
In addition, all synchroscopes shall include two synchronizing
lamps. These lamps shall be “bright” for synchronized conditions but are to
act solely as a supplementary indication that may be used by the operation with
caution in the event of failure of the synchroscope.
Integrating metering shall be
provided where indicated on the specification drawings. These meters shall be
of the withdrawable flush-mounted type and comply with the relevant parts of
IEC 521 and BS 5685, Class 1.0 accuracy, and BS 37, Part 9. The meters shall include
cyclometer dial-type registers.
Approved test terminal blocks
of the three-phase type shall be provided for connecting in the circuit with each
meter being a portable testing meter.
Electrical Recording Instrument and Meters
Recording instruments shall
be of an approved type, and unless otherwise specified, shall have two chart
speeds of 25 mm and 50 mm per hour available for selection by means other than
changing connections. They shall be complete with sufficient charts and inks
for two years of work.
All instruments, meters,
recorders, and apparatus shall be capable of carrying their full load currents
without undue heating. They shall not be damaged by the passage of fault
currents within the rating of the associated switchgear through the primaries
of their corresponding instrument transformers.
All instruments, motors, and
apparatus shall be back connected and the metal cases shall be earthed.
All voltage circuits to
instruments shall be protected by a fuse in each unearthed phase of the circuit
placed as close as practicable to the main connection.
All power-factor indicators
in 3-phase circuits shall have the star point of their current coils brought
out to a separate terminal which shall be connected to the start point of the
instrument current transformer secondary windings.
All instruments and meters
associated with multi-ratio CTs shall be provided with sets of scales etc.
appropriate to each CT ratio. It shall be possible to replace the scales of
instruments without dismantling the instruments or interfering with any
tropicalization finish.
The Contractor shall provide
electrical instrument and meter schedules to include, manufacturer, type, designation, current and voltage rating, accuracy class, and circuit
designation.
It is definitely a great website with a nice topic It is definitely a great website with a nice topic Electrical generator or Generator. You write a great interesting blog and have some great contents. Well done! Keep such informational blog about Earthing Electrical Equipment Manufacturer
ReplyDelete