Restricted Working Period In Bangladeshi Electrical Project
Due to monsoon rain between July and
September, work may slowdown. Due to traffic, work along /across road has to
carefully plan.
The Contractor shall obtain reliable Information concerning the conditions appertaining to the working areas covered by this Contract and shall plan his work in accordance with local conditions.
The Contractor shall obtain reliable Information concerning the conditions appertaining to the working areas covered by this Contract and shall plan his work in accordance with local conditions.
SYSTEM ELECTRICAL PARAMETERS IN BANGLADESH
230 kV Transmission System in Bangladesh
Normal Service Voltage : 230 kV
Rated Voltage : 245 kV
Insulation Level -
Lightning Impulse Withstand : 1050 kV
50Hz dry 1 minute Withstand : 460 kV
Number of Phase : 3
Frequency : 50 Hz
Switchgear Symmetrical
Breaking Capacity : 40 kA,
3 sec
System Earthing
The 230/132 kV auto
transformers are solidly earthed
132 kV Transmission System in Bangladesh
Normal Service Voltage : 132 kV
Rated Voltage : 145 kV
Impulse Voltage Withstand
Level : 650 kV
Number of Phase : 3
Frequency : 50 Hz
Switchgear Symmetrical
Breaking Capacity : 31.5 kA,
3 sec
Voltage Stability Limits : ± 10% Volts
Frequency Stability Limits : 48-51 Hz
33 kV Transmission System in Bangladesh
Normal Service Voltage : 33 kV
Rated Voltage : 36 kV
Impulse Voltage Withstand
Level : 170 kV
Number of Phase : 3
Frequency : 50 Hz
Switchgear Symmetrical
Breaking Capacity : 25 kA,
3 sec
The 33 kV system is solidly earthed at some of the 132/33 kV
Grid substations and resistance earthed at some of the Grid substations.
At the Proposed 132/33 kV
sub-station the 33 kV systems will be resistance earthed.
11 KV Distribution Systems in Bangladesh
Normal Service Voltage : 11 KV
Rated Voltage : 12 KV
Impulse Voltage Withstand
Level : 75 KV
Number of Phase : 3
Frequency : 50 Hz
Switchgear Symmetrical
Breaking Capacity : 25 kA,
3 sec
System earthing : Solid Normal
Low Voltage AC System in Bangladesh
Normal Service Voltage : 400/230 volts
Rated Voltage : 415/240 volts
Number of Phase : 3 phase 4 wire
Frequency : 50Hz
Switchgear Symmetrical
Breaking Capacity : 22kA, 3 sec
System earthing : Solid
D.C System in Bangladesh
For D.C. motor driven auxiliaries, tripping, indicating
lamps and controls.
Normal battery voltage : 110V nominal for new sub-stations.
Tolerance on rated voltage : + 10%, -15%
Voltage at various existing sites : 30V, 48V, 110V, 220V, 250V.
For Supervisory and Telecommunications
Nominal System Voltage : 48V
Normal float charge voltage : 53V
Tolerance on rated voltage : +1V, -7V