Fig-Typical Medium Voltage Cable Joint |
Dry heating cycle test in accordance with IEC 60840
On the joint three heating cycles without voltage were
performed. Each heating cycle consisted of 8 h heating and 16 h of natural
cooling. During the last 2 h of each heating period the conductor reached a
temperature of at least 95 C (5 C
above the maximum rated temperature).
Result: The test was performed in a correct way.
Water immersion and heat cycling in accordance with IEC 60840
After the three dry heating cycles, mentioned under 3.1
the joint was immersed in water, at a depth of at least 1 meter at the highest
point of the outer protection. Then the joint was subjected to 20 heating
cycles. In each heating cycle the water around the joint was heated to a
temperature between 70 °C and 75 °C (between 15 °C and 20 °C below the maximum
rated temperature of the cable conductor) and kept on this temperature for at
least five hours. Hereafter the water was cooled down to a temperature less than
the ambient temperature +10 °C.
Result: The water immersion and the heat cycling did not give
reason for remarks.
DC voltage test on insulation joint in accordance with IEC 60840
After the water immersion and heat cycling, a voltage
of 20 kV DC was applied for 1 minute between the metallic screen and the earthed
exterior of the joint outer protection. Hereafter a voltage of 20 kV, DC was
applied for 1 minute between the metallic screens on both sides of the joint.
The test was carried out while the test installation was at ambient temperature.
Result: No breakdown occurred.
Impulse withstand voltage test on insulation between the screens and water in accordance with IEC 60840
Sponsored:
After the above mentioned tests the test set-up was
tested with an impulse voltage of 37.5 kV. The test voltage was applied between
the metallic screen and the earthed exterior of the joint outer protection. The test was carried out while the test
installation was at ambient temperature. The test was carried out in accordance with IEC 60230. The joint was
tested with ten positive and ten negative voltage impulses.
Result: No breakdown occurred.
Impulse withstand voltage test on sheath sectionalizing insulation in accordance with IEC 60840
After the above mentioned tests the joint was taken out
the water and the sheath sectionalizing insulation was tested with an impulse
voltage of 75 kV. The test voltage was applied between the metallic screens on
both sides of the joint. The test was carried out while the test installation
was at ambient temperature. The
test was carried out in accordance with IEC 60230. The joint was tested with ten
positive and ten negative voltage impulses.
Result: No breakdown occurred
Examination of the joint in accordance with IEC 60840
The joint was dismantled and inspected for water
penetration and cracks.
Result: No signs of cracks or water penetration were detected.
The construction of the joint complied with the construction
drawing.
Hope this article on TEST OF THE OUTER PROTECTION OF THE BURRIED JOINT IN
ACCORDANCE WITH IEC 60840 is helpful for you and your friends. If you think it’s
need some add, put your comments below- comment
space.
Nice Post,I really like this Blog,I got Lot Of information from this Blog. For some More Information please visit our website lightning arrester ratings
ReplyDeleteGreat Blog,Thanks for sharing such beautiful information with us.We have some more information about this lightning arrester ratings. Please visit our site lightning arrester ratings.
ReplyDelete