Generally, an Earthing or Grounding Transformer is not a three-phase transformer, but a single-phase transformer with the primary (HV end)
rated voltage equal to the system phase-to-neutral voltage and the secondary
(LV end) rated voltage of either 240V or 11oV.
To avoid any switching transient in the Transformer primary
of the transmission system, or a big noise may damage the Transformer. To avoid
such spurious signal grounding is provided in the primary. The grounding
also affects third harmonics from switching transient.
The reason why a grounding or earthing transformer is needed
in large or heavy-duty power transformers is that a grounding of a transformer
allows the power grid to have a common point of reference for the voltages;
otherwise, the voltage may vary from place to place. Earthing or Grounding The transformer also allows for safety for both transformer and the people using power.
What is the Use of Earthing Transformers?
Generally grounding transformer or an earthing transformer is used to provide a ground path to either an ungrounded way or a delta-connected system.
- Earthing Transformer allows the connection of phase-to-neutral loads when desired.
- Earthing the transformer provides a relatively low-impedance path to the ground maintaining the system neutral or ground potential;
- During re-striking ground fault Earthing Transformer limits the magnitude of transient over-voltages;
- During line-to-ground faults Earthing Transformer supplies a source of ground fault current;
You may like to read:
"Transformer Capacity and Rating"
Electrical point of view ground and earth are same.
We can assume that earth is not a super conductor but has a zero resistance. So it can act as a big collecting basin for unwanted voltages and currents what is the function of earthing.
Typically Earth line is connected locally to ground and neutral line goes back to transformer. Neutral provides close circuit path for current. While Earthing provide safety and protection for use.
In star connection there is only one neutral line, which is consider as a reference voltage that is may be not zero.
Why Earthing or Grounding Transformer is Required for Electrical Energy Transmission Grid?
Sponsored:
Understanding the requirement of Earthing Transformer or Grounding Transformer in the large power transmission grid, we would like to investigate the following case study-
Why Earthing or Grounding The transformer is required, of course for economic reasons; let us see: for example, we are dealing with an 11kV system, whose neutral we want to ground through a resistance.
Let's consider the desired ground-fault current is 10A. Now, if we want to connect a resistor in the path between
the system neutral and earth, the calculated value of the resistor would be
(6350/10 = 635 Ohms), and the rated voltage would be 6350V (11,000/1.732=6350). Easily
we can observe that practically 6350 V rated a 635 Ohms resistor would be very
costly and not economical.
But, if we choose for a single-phase 6350V/240V (input
voltage 6350 Volt and output 240 Volt) neutral grounding transformer, whose
6350V winding is connected at neutral to the ground path. In this case, we can
connect a simple 0.9 Ohms resistor across the 240V secondary of this neutral
grounding transformer.
Here 0.9 Ohms resistor connected at 240V side will reflect as
700 ohms [Square (6350/240) = 700]. The 0.9 Ohms resistor connecting at
grounding transformer secondary 240 volts we will get reflected 630 ohms (700x0.9=
630). So, the advantage is that this resistor needs to be insulated only for
240V. Reduced the insulation level of resistor means cheaper the cost, the result
is an economic system.
A grounding transformer or earthing transformer is one kind of auxiliary transformer that is used in three-phase electric power transmission systems to provide a ground or earth path. In short, we can say Earthing or Grounding Transformers are part of an earthing system of the electrical transmission network.
Download the Earthing Transformer PDF copy of Earthing Transformer design or Grounding Transformer design guide:
Free DOWNLOAD
Sponsored:
Types of Earthing Transformer
The following two types of earthing transformers are generally used grounding transformer is used to provide a low impedance path to the neutral and also limits the transient overvoltage to the system when the system neutral is not available:
- delta-star grounding transformer;
- zig-zag grounding transformer.
You may know the details about the electrical transformer from the following articles:
- Working Principle of Transformer;
- Transformer Construction;
- Core-type Transformers;
- Shell-type Transformers;
- Elementary Theory of an Ideal Transformer;
- E.M.F. Equation of Transformer;
- Voltage Transformation Ratio;
- Transformer with losses but no Magnetic Leakage;
- Transformer on No-load;
- Transformer on Load;
- Transformer with Winding Resistance but no Magnetic Leakage;
- Equivalent Resistance;
- Magnetic Leakage;
- Transformer with Resistance and Leakage Reactance;
- Simplified Diagram;
- Total Approximate Voltage Drop in Transformer;
- Exact Voltage Drop;
- Equivalent Circuit Transformer Tests;
- Open-circuit or No-load Test;
- Separation of Core Losses;
- Short-Circuit or Impedance Test;
- Why Transformer Rating in KVA?;
- Regulation of a Transformer;
- Percentage Resistance, Reactance, and Impedance;
- Kapp Regulation Diagram;
- Sumpner or Back-to-back-Test;
- The efficiency of a Transformer;
- Condition for Maximum Efficiency;
- Variation of Efficiency with Power Factor;
- All-day Efficiency;
- Auto-transformer;
- Conversion of 2-Winding Transformer into Auto-transformer;
- Parallel Operation of Single-phase Transformers;
- Questions and Answers on Transformers;
- Three-phase Transformers;
- Three-phase Transformer Connections;
- Star/Star or Y/Y Connection;
- Delta-Delta or ∆/∆ Connection;
- Wye/Delta or Y/ Connection;
- Delta/Wye or ∆/Y Connection;
- Open-Delta or V-V Connection;
- Power Supplied by V-V Bank;
- Scott Connection or T-T Connection;
- Three-phase to Two-Phase Conversion and vice-versa;
- Parallel Operation of 3-phase Transformers;
- Instrument Transformers;
- Current Transformers;
- Potential or Voltage Transformers.
NGR is important to a trnasformer earthing. NGR(Neutral Grounding Resistor) is nothing but a high resistance grounding which in context of electrical power system means the grounding of the system
ReplyDeleteneutral through a resistance which limits ground-fault current to a value equal to , or slightly greater than the capacitive charging current of that system.
Hi there friends, how is everything, and what you want to say on the topic of this post,
ReplyDeletein my view its in fact amazing in support of me.
Wow its a very good post. The information provided by you is really very good and helpful for me. Keep sharing good information.
ReplyDeleteEarthing method prevents excessive current from flowing through the circuit in order to protect electrical appliances and devices. Every substation needs a properly designed earthing system. Substations are a potential source of electrical hazards for maintenance personnel and end users due to poorly installed electrical equipment and ineffective earthing systems. Current-carrying parts of electrical equipment can be earthed by connecting them to the earth. Transformers in substations are the most expensive equipment. Therefore, it must be protected from damage and malfunction. Thanks a lot for sharing such a valuable writing piece.
ReplyDeleteThank you for sharing such fruitful content with us.
ReplyDeleteTractor Price
Grateful for the rich and informative content you’ve shared with us!
ReplyDeleteMystery Shopping Company in India